Product description:
Automatic diesel generating set
It is designed with the advanced control system, using special program controller, and advanced ATS as the core of the high performance digital, automatic generating sets.
Products from the 10KW-5000KW units in the unattended condition automatically realize start-up and shutdown, automatic switching electricity and electricity network, automatic monitoring the running state of equipment, product technology, reliable quality and superior performance, over the years the products become the leader in automation units, exports of the country come out in front.
Introduces the performance
1, automatic start and input function
When the city electricity grid to stop power supply or mains voltage or less than 80% of the rated value unit will start automatically, after a successful start-up, to supply the power to the load, the entire process of successful control within 15 seconds of a start, having a distal end interface, can set the start delay, the realization of generating unit start and stop automatically.
2, automatic exit function
Generator power output from during the automatic state, if the city electricity recovery and after 30 seconds after the confirmation, unit start executing automatically exit the program, set will be the first to cut off the load, recovery of electric power supply, and cooler running automatically stop after 2 minutes.
If the cooler during the operation, the city power to stop power supply, is set automatically adjustable high speed, on the recovery of load power supply.
3, alarm in advance / fault protection function
Low battery voltage, charge failure, over current, low oil pressure, water temperature higher with early warning function, i.e. not numerical stop in alarm, alarm light flashes at this time; when the value exceeds the value of the oil machine downtime, and downtime fault generated.
Low speed, speed, frequency of out of gauge, voltage limit, emergency stop, failed to start a fault protection function, if an analog input value is greater than or less than the lower limit upper limit, corresponding to the high / low start delay, delay after the end, numerical throw did not return to normal, oil machine immediately fault shutdown, warning light on.
The above all kinds of alarm signal has the self-locking function, only the scene personnel after troubleshooting, press the "stop" button will make the system back to normal.
4, automatic charging function
Since the power unit in electric or period, automatic charging of battery for starting control.
The charging system uses switch power supply, it can realize two stage charging method of battery.
In the first stage of charging, the battery capacity is low, using 6ADC with constant current charging, when the battery voltage to the 26.5VDC to the constant voltage charging, and remained floating charge.
When the battery was fully charged, the charging current automatic zero.
5, the manual function
The unit control system panel has automatic and manual, when system is working in manual state, can be realized on the start-up, high and low speed loaded, power supply, stop, alarm signal lamp test alarm since lifting the power opening and closing, the closing operation, electric.
Emergency stop knobs are effective in automatic and manual state.
Very urgent situation, do not use this button.
6, other functional overview
The use of animation icon type alarm, fault display, high brightness, multicolor liquid crystal display parameters; automatic recording unit running time; compact and reasonable structure, stable and reliable performance.
|